Resolution A.952(23)
Adopted on 5 December 2003
(Agenda item 17)
GRAPHICAL SYMBOLS FOR SHIPBOARD FIRE CONTROL PLANS
T
HE
A
SSEMBLY
,
R
ECALLING
Article 15(i) of the Convention on the International Maritime Organization concerning the
functions of the Assembly in relation to regulations and guidelines concerning maritime safety,
B
EARING IN MIND
that regulation II-2/15.2.4 of the International Convention for the Safety of Life at Sea
(SOLAS), 1974, as amended, requires that fire control plans be permanently exhibited for the guidance of
the ship’s officers and that a duplicate set of fire control plans or a booklet containing such plans be
permanently stored in a prominently marked weathertight enclosure outside the deckhouse for the
assistance of shore-side fire-fighting personnel,
R
ECOGNIZING
that the use of international symbols for shipboard fire control plans would greatly increase
their usefulness, both for the crew of the ship and for shore-based fire brigades,
R
ECALLING ALSO
resolution A.654(16) on Graphical symbols for fire control plans,
N
OTING
that ISO had, in close co-operation with IMO, developed standard ISO 17631:2002 – Ships and
marine technology – Shipboard plans for fire protection, life-saving appliances and means of escape,
providing fire protection symbols which generally conform to the corresponding symbols set out in
resolution A.654(16),
N
OTING IN PARTICULAR
that, through MSC/Circ.1050, Member Governments had been invited to bring
standard ISO 17631:2002 to the attention of shipbuilders, shipowners, shipoperators, shipmasters, shore-
based fire-fighting personnel and other parties concerned with the preparation or use of shipboard fire
control plans, so that they might use it, on a voluntary basis, for the preparation or use of the shipboard fire
control plans required by SOLAS regulation II-2/15.2.4, pending the outcome of the work related to the
revision of resolution A.654(16),
H
AVING CONSIDERED
the recommendation made by the Maritime Safety Committee at its seventy-seventh
session,
1. A
DOPTS
the Graphical symbols for shipboard fire control plans, set out in the annex to the present
resolution;
2. U
RGES
Governments to bring the aforementioned graphical symbols to the attention of shipbuilders,
shipowners, shipoperators, shipmasters, shore-based fire-fighting personnel and other parties concerned
with the preparation or use of shipboard fire control plans with a view to encouraging their use for the
preparation of
the shipboard fire control plans required by SOLAS regulation II-2/15.2.4,
for ships
constructed on or after 1 January 2004;
3. I
NVITES
Governments to bring standard ISO 17631:2002 to the attention of shipbuilders, shipowners,
shipoperators and shipmasters so that they may use the additional guidance contained therein for the
preparation of shipboard fire control plans;
4. A
GREES
that ships constructed before 1 January 2004 may continue to carry fire control plans that use
the graphical symbols contained in resolution A.654(16);
5. R
EQUESTS
the Maritime Safety Committee to keep this resolution under review and to amend it as
necessary.
Resolution A.952(23) — 173
Annex
GRAPHICAL SYMBOLS FOR SHIPBOARD FIRE CONTROL PLANS*
Graphical symbols for structural fire protection
Graphical
symbol
No.
Reference
Comments on use
1.1
A-class division
1.2
B-class division
Main vertical
zone
1.3
The symbol should be at the door position and should
show the actual direction of the door.
Add WT to the right side of the symbol in the case of a
watertight door.
Add SWT to the right side of the symbol in the case of a
semi-watertight door.
A-class hinged
fire door
1.4
The symbol should be at the door position and should
show the actual direction of the door.
Add WT to the right side of the symbol in the case of a
watertight door.
Add SWT to the right side of the symbol in the case of a
semi-watertight door.
B-class hinged
fire door
1.5
The symbol should be at the door position and should
show the actual direction of the door.
Add WT to the right side of the symbol in the case of a
watertight door.
Add SWT to the right side of the symbol in the case of a
semi-watertight door.
A-class hinged
self-closing fire
door
1.6
The symbol should be at the door position and should
show the actual direction of the door.
Add WT to the right side of the symbol in the case of a
watertight door.
Add SWT to the right side of the symbol in the case of a
semi-watertight door.
B-class hinged
self-closing fire
door
1.7
* A legend of symbols and explanations should be a constituent part of any fire control plan and contain a list of the graphical
symbols used in the plan, together with the appropriate explanations, and may include additional special information such as
the type of extinguishing media used in fixed fire-extinguishing systems.
174 — Resolution A.952(23)
Graphical
symbol
No.
Reference
Comments on use
The symbol should be at the door position and should
show the actual direction of the door.
Add WT to the right side of the symbol in the case of a
watertight door.
Add SWT to the right side of the symbol in the case of a
semi-watertight door.
A-class sliding
fire door
1.8
The symbol should be at the door position and should
show the actual direction of the door.
Add WT to the right side of the symbol in the case of a
watertight door.
Add SWT to the right side of the symbol in the case of a
semi-watertight door.
B-class sliding
fire door
1.9
The symbol should be at the door position and should
show the actual direction of the door.
Add WT to the right side of the symbol in the case of a
watertight door.
Add SWT to the right side of the symbol in the case of a
semi-watertight door.
A-class self-
closing sliding
fire door
1.10
The symbol should be at the door position and should
show the actual direction of the door.
Add WT to the right side of the symbol in the case of a
watertight door.
Add SWT to the right side of the symbol in the case of a
semi-watertight door.
B-class self-
closing sliding
fire door
1.11
Colour of the circle and a letter at the right side of the
symbol should indicate as follows:
A = blue for accommodation and service spaces;
M = green for machinery spaces;
C = yellow for cargo spaces.
Ventilation
remote control
or shut-off
1.12
Remote control
for skylight
1.13
Remote control
for watertight
doors or fire
doors
Add WT to the right side of the symbol to indicate
remote control for watertight doors or FD to indicate
remote control for fire doors.
1.14
Colour of the circle and a letter at the right side of the
symbol should indicate as follows:
A = blue for accommodation and service spaces;
M = green for machinery spaces;
C = yellow for cargo spaces.
Identification number of the damper may be shown at
the bottom of the symbol.
1.15
Fire damper
Resolution A.952(23) — 175
Graphical
symbol
No.
Reference
Comments on use
Colour of the circle and a letter at the right side of the
symbol should indicate as follows:
A = blue for accommodation and service spaces;
M = green for machinery spaces;
C = yellow for cargo spaces.
Identification number of the closing device may be
shown at the bottom of the symbol.
Closing device
for ventilation
inlet or outlet
1.16
Colour of the circle and a letter at the right side of the
symbol should indicate as follows:
A = blue for accommodation and service spaces;
M = green for machinery spaces;
C = yellow for cargo spaces.
Identification number of the damper may be shown.
Remote control
for fire
damper(s)
1.17
Colour of the circle and a letter at the right side of the
symbol should indicate as follows:
A = blue for accommodation and service spaces;
M = green for machinery spaces;
C = yellow for cargo spaces.
Identification number of the closing device(s) may be
shown.
Remote control
for closing
device(s) for
ventilation inlet
and outlet
1.18
Graphical symbols for fire-protection appliances
Graphical
symbol
No.
Reference
Comments on use
Fire protection
appliances or
structural fire
protection plan
2.1
Remote control
for fire pump(s)
2.2
The type, quantity of water delivered per time unit, and
pressure head should be indicated either at the right
side of the symbol or in the legend.
2.3
Fire pump(s)
Remote control
for emergency
fire pump or fire
pump supplied
by the
emergency
source of power
2.4
The type, quantity of water delivered per time unit, and
pressure head should be indicated either at the right
side of the symbol or in the legend.
Emergency fire
pump
2.5
176 — Resolution A.952(23)
Graphical
symbol
No.
Reference
Comments on use
Fuel pump(s)
remote shut-off
2.6
Lube oil pump(s)
remote shut-off
2.7
Remote control
for bilge
pump(s)
2.8
Remote control
for emergency
bilge pump
2.9
Remote control
for fuel oil valves
2.10
Remote control
for lube oil
valves
2.11
Remote control
for fire pump
valve(s)
2.12
Indicate at the bottom of the symbol the protected
space. Extinguishing media should be colour coded in
the lower part of the symbol and be indicated by a letter
at the right side of the symbol as follows: grey – CO
2
for
carbon dioxide or N for nitrogen, brown – H for gas
other than CO
2
or N (type of gas to be indicated),
white – P for powder, green – W for water.
Remote release
station
2.13
International
shore
connection
2.14
Resolution A.952(23) — 177
Plik z chomika:
Januszek66
Inne pliki z tego folderu:
Back Seat_ A Mumbai Tale - Aditya Kripalani.mobi
(755 KB)
Brief Wondrous Life of Oscar Wao, The - Junot Diaz.opf
(3 KB)
Don't Make Me Think, Revisited_ - Steve Krug.mobi
(9256 KB)
M. T. Anderson - Norumbegan 03 - The Empire of Gut and Bone # (v5.0).epub
(2209 KB)
M. T. Anderson - Norumbegan 02 - The Suburb Beyond the Stars # (v5.0).epub
(2105 KB)
Inne foldery tego chomika:
Dokumenty
Galeria
LUDLUM ROBERT
Midi - Kar
Mszał Rzymski PL
Zgłoś jeśli
naruszono regulamin