102E5
electronic mini-
programmer for
controlling hot water
and heating
Installation & User Instructions
including Factory Replacement Units (FRU)
Index
Installation
Product specifi cation
3
Installation
4-6
Wiring
6-9
Replacement
10-11
User
Your programmer
12
Setting the clock
13
Factory preset programmes
14
Setting the programme - 24 hour
15
Setting the programme - 5/2 day
16
Running the programme
17
Temporary user overrides
18
Battery backup
19
Contact details
20
2
Installation Instructions
Please Note:
This product should only be installed by a qualifi ed
electrician or competent heating installer, and
should be in accordance with the current edition of
the IEEE wiring regulations.
Product specifi cation
Specifi cation
Power supply
230 ± 15% Vac, 50 Hz
Switching action
1 x SPST, Type 1B
Switch rating
264 Vac, 50/60Hz, 3(1)A
Timing Accuracy
±1 min./month
Power Reserve
Minimum 14 days
Enclosure Rating
IP30
Max. Ambient Temperature
45°C
Dimensions, mm (W, H, D)
103 x 137 x 48
Design standard
EN 60730-2-7
Control Pollution Situation
Degree 2
Rated Impulse Voltage
2.5kV
Ball Pressure Test
75°C
3
Installation
NB. For FRU units - go straight to point 6 below.
1.
Loosen the fi xing screw in the base of the unit to release
the Wiring Cover.
2.
Holding the unit face downwards, press fi rmly in the
centre of the wallplate and slide it apart and lift it from
the module.
3.
Fix the wallplate and terminal block to the wall, or
plaster box, as required. Ensure that the screw heads
do not protrude beyond the vertical centre rib of the
wallplate, or this will prevent the module correctly
locating onto the wallplate.
Screw fi xing holes
(screwheads MUST
NOT protrude
above centre rib)
Vertical centre rib
Wallplate & Terminals
4. Surface cables can only enter from below the unit. Cut
an appropriate cable aperture in the wiring cover. If the
wallplate is mounted on a plaster box, cables can enter
from the rear below the terminal block.
4
5. Electrical connections are simplifi ed by using a Wiring
Centre. However, if this is not used, the wallplate
terminal identifi cation is as shown.
Water
Heating
Mains Supply
(via 3 amp fuse)
ON
ON
COM
N
L
1
2
3
5
6
If the system being controlled is 230Vac then terminals
3 and L must be linked with insulated cable capable
of carrying full load current. Whilst the unit does not
require an earth connection, a terminal is provided on
the wallplate for earth continuity purposes.
6. Referring to the wiring diagrams on page 6-9, connect
the unit as shown.
7. Find out from the user whether the unit is required
to operate in 24-hour mode (factory preset) or
weekday/weekend mode (5/2 day). To convert to 5/2
day mode remove the small two-way connector from
the pins towards the left of the recess on the rear of
the module, then press the
SELECT/ADVANCE/+/-
buttons all at the same time to RESET the unit.
8. Ensure all dust and debris are cleared from the area.
Plug the module into the wallplate by locating it onto
the wallplate and, when fl ush with it, sliding it down,
ensure the hook at the top of the wallplate engages
with the slot at the back of the module.
9. Before setting the programme, check the unit and circuit.
Set the rocker switch to
WATER & HEATING
. Press the
SELECT
button until the bar in the display lines up with
the word
ON.
Adjust the remote thermostats to check the
system operates correctly.
5
Plik z chomika:
januszmaka
Inne pliki z tego folderu:
Model 102.pdf
(238 KB)
Model 102E5.pdf
(232 KB)
Model 102E7.pdf
(280 KB)
Model 103.pdf
(238 KB)
Model 103E5.pdf
(234 KB)
Inne foldery tego chomika:
CP715
FP715
Mk3 programmers
Replacement time controls
SET1E
Zgłoś jeśli
naruszono regulamin